560kVA Cast Resin Dry Type Isolation Transformer 440V to 390Y/225V with IEC60076 Standard
| Brand Name: | WINLEY |
| Model Number: | SCB10-560/0.44 |
| MOQ: | 1unit |
| Price: | $1000-$100000 |
| Packaging Details: | Plywood case |
| Payment Terms: | T/T |
Best for:
Cabinet-integrated indoor power systems, industrial equipment and high-humidity or coastal projects requiring 560kVA cast resin dry type isolation from 440V to 390Y/225V.
Customizable Specifications:
kVA, primary voltage, secondary voltage, frequency, vector group, enclosure/IP requirement, cooling method, tap range, ambient condition, altitude, quantity, destination port and required accessories.
This 560kVA cast resin dry type isolation transformer is designed for cabinet-integrated indoor power systems, industrial equipment power supply, and high-humidity or coastal projects where moisture exposure and fire behavior need to be considered. It converts 440V Delta input to 390Y/225V Wye-N output, making it suitable for three-phase systems that require a neutral connection.
The transformer uses cast resin windings, copper conductors, a silicon steel core, F-class insulation, and C2 / E2 / F1 dry type classification. Its AN/AF cooling arrangement includes natural air cooling and fan-assisted heat dissipation for indoor operating conditions. The IP00 open structure is intended for installation inside an electrical cabinet, enclosure, or integrated power system.
With Dyn11 connection, five-position primary-side tapping, and IEC60076 design basis, this unit provides clear parameters for project selection, electrical room layout, equipment integration, and voltage matching during commissioning.
Product Photos
![]()
![]()
![]()
Main Data
| Item | Data |
|---|---|
| Product type | Cast resin dry type isolation transformer |
| Rated capacity | 560kVA |
| Phase | 3 Phase |
| Primary voltage | 440V |
| Secondary voltage | 390Y/225V |
| Frequency | 50Hz |
| Vector group | Dyn11 |
| Cooling method | AN/AF |
| Winding material | Copper |
| Insulation class | F, 155℃ |
| Temperature rise | 100K |
| No-load loss | 1460W, 10% tolerance |
| Load loss | 6310W at 120℃ |
| Accessories | Cooling fans and temperature controller with PT100 sensors |
| Dimensions | 1200 × 1250 × 1320mm |
| Weight | 1766kg |
Technical drawings
![]()
Standard Features
- Cast resin windings: Provide an oil-free insulation structure for indoor electrical rooms, equipment cabinets and integrated power systems.
- F-class insulation with C2 / E2 / F1 rating: Supports indoor projects where temperature rise, humidity exposure and fire behavior need to be considered.
- Copper winding and silicon steel core: Matched with the 560kVA rating and 440V to 390Y/225V voltage conversion.
- AN/AF cooling system: Natural air cooling with fan-assisted forced air cooling for additional heat dissipation.
- Temperature control system: Temperature controller and PT100 sensors help monitor winding temperature during operation.
- Five-position tap terminals: 418V / 429V / 440V / 451V / 462V tapping allows voltage adjustment during commissioning.
- IP00 open structure: Suitable for installation inside an electrical room, enclosure or customer-provided cabinet.
- Dry type installation: No insulating oil is used, so oil pit planning is not required where the project design permits.
| Sector | Applications |
|---|---|
| High-humidity or coastal projects | Power conversion for projects where moisture exposure needs to be considered, with installation inside an enclosure or electrical cabinet. |
| Indoor electrical rooms | Low-voltage transformer installation for controlled electrical rooms, switchgear rooms and equipment areas. |
| Industrial equipment systems | Production lines, machinery systems and OEM equipment requiring 440V Delta to 390Y/225V Wye-N conversion. |
| Fire-sensitive indoor areas | Oil-free dry type transformer application for buildings or equipment rooms where liquid-filled transformers are not preferred. |
| Cabinet-integrated power systems | Transformer integration for packaged power systems, control cabinets and equipment-mounted power units. |
|
Rated capacity |
High Voltage |
Low |
Connection Symbol |
No-Load Loss |
On-Load Loss |
No Load Current |
Weight |
Dimension L*W*H(mm)
|
|
100 |
6 6.3 10 10.5 11 |
0.4 |
Dyn11 |
540 |
1990 |
2.4 |
520 |
1600*1300*2200 |
|
315 |
970 |
4080 |
1.8 |
1085 |
1800*1350*2200 |
|||
|
500 |
1350 |
5790 |
1.8 |
1520 |
2000*1400*2200 |
|||
|
630 |
1530 |
6840 |
1.6 |
1820 |
2000*1400*2200 |
|||
|
1000 |
2070 |
9780 |
1.4 |
2550 |
2450*1450*2200 |
|||
|
1250 |
2380 |
11500 |
1.4 |
2900 |
2300*1500*2200 |
|||
|
1600 |
2790 |
13800 |
1.4 |
3490 |
2400*1550*2200 |
|||
|
2000 |
3240 |
16300 |
1.2 |
4220 |
2600*1600*2200 |
|||
|
2500 |
3870 |
19300 |
1.2 |
4955 |
2600*1600*2200 |
![]()