25kVA Single Phase Pole Mounted Transformer 14.4kV/7.2kV to 120/240V Overhead Utility Distribution Type CSA Standard cUL Listed
| Brand Name: | WINLEY |
| Model Number: | D11-25/24.94(12.47)/0.12-0.24 |
| MOQ: | 1unit |
| Price: | $1000-$100000 |
| Packaging Details: | Plywood case |
| Payment Terms: | T/T |
1. Winley Electric pole-mounted distribution transformers are UL and cUL Listed under File No. E543292, with ratings from 10 kVA through 500 kVA. They are built to meet or exceed applicable requirements of ANSI/IEEE, CSA, DOE 2016, and IEC 60076 standards.
2. Winley Electric pole-mounted transformers can be flexibly customized to meet project requirements. Customer-specified accessory brands, such as Eaton Cooper Power series and Qualitrol, can also be provided upon request.
3. Winley Electric transformers are supplied to global markets, including North America, South America, and Southeast Asia. Backed by decades of industry experience, we deliver safe, reliable, and efficient transformer designs with comprehensive technical support.
![]()
The WINLEY 25 kVA Single Phase Pole Mounted Transformer provides a reliable, high-performance solution for overhead utility networks and rural power distribution. Engineered to convert 24940GrdY/14400V or 12470GrdY/7200V primary voltages down to a 120/240V secondary output, this oil-immersed (ONAN) unit fully complies with Canadian standards CSA C2.2-06 and CSA 802, making it an ideal choice for standard grid integrations. Its compact pole-mounted configuration allows for highly efficient installation and immediate deployment in regional overhead systems.
Built with an integrated dual-voltage switch and a 5-position off-circuit tap changer (±2 × 2.5%), this transformer delivers exceptional operational versatility. This feature enables utilities to standardize a single transformer type across diverse multi-voltage networks, significantly reducing procurement inventory overhead while ensuring precise local voltage regulation. Backed by a 125kV BIL high-voltage bushing and certified low-loss performance, it directly secures long-term cost savings and operational stability for contractors and utility operators.
Product Photos
![]()
![]()
![]()
![]()
![]()
Main Data
| Item | Data |
|---|---|
| Product type | Single Phase Pole Mounted Transformer |
| Rated capacity | 25 kVA |
| Phase | 1 phase |
| Primary voltage | 14.4kV / 7.2kV |
| Secondary voltage | 120/240V |
| Rated current | 1.7A / 3.5A primary; 104.2A / 208.3A secondary |
| Winding material | Aluminum |
| Frequency | 60Hz |
| HV BIL / LV BIL | HV LI125(95) AC40(34); LV LI30 AC10 |
| Cooling method | ONAN |
| Temperature rise | 65°C |
| No-load loss | 70.9W |
| Load loss | 230.4W at 85°C |
| Short-circuit impedance | 2.30% at 85°C |
| Total mass | 320 kg |
| Dimensions | 596 × 669 × 1160 mm |
Technical drawings
![]()
Standard Features
- HV Bushings Insulated terminal for high-voltage conductor connection.
- LV Bushings X1, X2 and X3 insulated low-voltage terminals.
- Tap Changer Adjusts winding taps to regulate the output voltage.
- Top Cover Sealed cover protecting the oil-filled tank opening.
- Lifting Lugs Steel lugs for pole mounting and mechanical support.
- Mounting Bracket Side brackets for securing the unit to a pole.
- Grounding Strap Neutral grounding strap for safe low-voltage connection.
- Grounding Terminal Earthing point for protective grounding of the tank.
- Nameplate Displays the transformer’s key ratings and identification information.
- Utility Distribution Points
Suitable for utility pole-mounted distribution service where 14.4kV or 7.2kV primary voltage needs to be stepped down to 120/240V. - Rural Overhead Distribution
Used for farms, rural residences, remote service points, and low-density distribution areas requiring reliable single-phase power supply. - Small Commercial Service Loads
The 25kVA capacity and 120/240V output can support small commercial buildings, outdoor equipment loads, lighting circuits, and service entrances. - Light Industrial Auxiliary Power
Suitable for auxiliary single-phase loads in light industrial sites where overhead medium-voltage distribution is available. - Outdoor Distribution Replacement Projects
The pole-mounted oil-filled format fits transformer replacement, feeder extension, and utility maintenance programs.
| Rated Capacity (kVA) | High Voltage (kV) | No Load Loss (W) | On Load Loss (W) | Height (mm) | Depth (mm) | Width (mm) | Weight (kg) |
| 15kVA |
34.5/19.92 13.8/7.96 13.2/7.6 12.47/7.2 or others |
50 | 195 | 840 | 740 | 610 | 294 |
| 25kVA | 80 | 290 | 840 | 740 | 610 | 362 | |
| 37.5kVA | 106 | 360 | 840 | 760 | 610 | 476 | |
| 50kVA | 135 | 500 | 840 | 810 | 610 | 553 | |
| 75kVA | 190 | 650 | 840 | 860 | 610 | 672 | |
| 100kVA | 280 | 1010 | 910 | 1200 | 965 | 714 | |
| 167kVA | 435 | 1530 | 1000 | 1200 | 965 | 913 | |
| 250kVA | 550 | 2230 | 1250 | 1300 | 1430 | 1106 |
![]()
![]()