Substation transformer

2025-03-11

WINLEY’s substation transformers are designed, built, and tested in accordance with the highest industry standards including NEMA, ANSI C.57, DOE, and IEEE as applicable, The capacity ranges from 150Kva to 20000Kva, the primary voltage range is usually 2.4KV-69KV, and the secondary voltage range is usually 0.6KV-35KV, widely used in various utilities or small industrial scenarios.

 

latest company news about Substation transformer  0

 

 

WINLEY’s substation transformers are designed, built, and tested in accordance with the highest industry standards including NEMA, ANSI C.57, DOE, and IEEE as applicable, These substation transformers are absorb and utilize advanced domestic and foreign technologies to optimize the transformer core, coil, body, lead wire, oil tank and other components. They have the characteristics of low partial discharge, low loss, low noise, light weight and long service life.

 


 

Design capabilities

 

Capacity 150Kva-20000Kva
Primary Vollage 2.4kV/4.16kV/4.8kV/6.9kV/7.2kV/12kV/12.47kV/13.2kV/13.8kV/23kV/34.5kV/44KV/69KV or other
Secondary Voltage 208Y/240/480/600/2400/4160Y/4800/12000/12470/13200/13800 or other
Connection type Dyn1Dyn11YNd1Dd0
Insulation Fluids ONAN / ONAFKNAN / KNKF
Frequency 50Hz、60Hz
BIL 30V-250V
Standards ANSI/IEEE C57
CSA
NEMA
ASTM

 

Substation transformer structure

 

WINLEY’s substation transformers incorporate advanced domestic and foreign technologies to optimize components such as the transformer core, coil, body, lead wire, and oil tank. These transformers are characterized by low partial discharge, low loss, low noise, lightweight, and long service life. They are designed for installation in both large and small three-phase transmission and distribution power systems.

 

latest company news about Substation transformer  1

 

Substation transformer Standard Features

 

  • Electrical grade mineral insulating oil
  • High-grade silicon-steel core
  • Aluminum windings (distribution class)
  • On-load tap changer
  • Reinforced carbon steel tank
  • Lifting lugs
  • Externally clamped high- and low-voltage bushings
  • Pressure relief valve
  • Pressure vacuum gauge
  • Liquid temp gauge
  • Liquid level gauge
  • Drain and sample valve
  • Schrader valve
  • Ground pads/lugs
  • Nitrogen blanket
  • 65 degree C rise

Substation transformer Optional Features

  • Environmentally friendly, high fire-point FR3 oil (KNAN)
  • Copper windings
  • On-load tap changer
  • Stainless steel tank
  • Gauges with contacts
  • Auxiliary control cabinet
  • Winding temperature indicator
  • Fan package (ONAN/ONAF)
  • Lid-mounted pressure relief device
  • Sudden pressure relay
  • Lightning arresters
  • 55/65 degree C rise
  • Step-up solar and wind duty design
  • Electrostatic shielding
  • K-rated design
  • Primary load-interrupter switch

 

Substation transformer drawing

 

Substation transformer high-voltage and low-voltage cables connect through bushings on the throat-type side end or the top, while their flexible core/coil and tank construction ensure that dimensional requirements can be met.

 

latest company news about Substation transformer  2

 

Substation transformer Specification

 

Rated Capacity High Voltage Low Voltage Connection Symbol Short Circuit Impendence No-load loss On-load loss Dimension Weight
(kVA) (KV) (V)   (%) (W) (W)

W*H*D

mm

kg
800 4.16KV
12.47KV
13.2KV
13.8KV
24.94KV
34.5KV
or others
208/120V
480/277V
600V
12470V
13200V
13800V
or others
Dyn1
Ynyn0
Dyn11
Dd0
Ynd11
or others
2.7
3.1
4.35
5.75
6
980 9350 1060*1500*1780 2050
1000 1160 11500 1085*1570*1800 2450
1250 1380 13900 1160*1610*1890 2900
1600 1660 16600 1190*1630*1950 3400
2000 2030 18300 1260*1700*2090 4100
2500 2450 19600 1150*2150*2250 4750
3000 3240 26500 1900*2600*2150 6500
5000 4500 27000 2500*2210*3180 9500
7500 7200 32000 3660*3100*5100 13600
10000 8500 35500 3830*2640*2216 15800

 

Testing


WINLEY performs routine testing on each transformer manufactured,including the following tests:
• Ratio, polarity, and phase relation:Ensures correct winding ratios and tap voltages; checks insulation of HV and LV circuits; checks entire insulation system to verify all live-to ground clearances.
• Winding resistance:Verifies the integrity of internal high-voltage and low-voltage connections; provides data for loss upgrade calculations
• Insulation power factor:Verifies that vacuum processing has thoroughly dried the insulation system to required limits
• Routine impulse tests:The most severe test, simulating a lightning surge;applies one reduced wave and one full wave to verify the BIL rating
• Applied potential: Applied to both high-voltage and low-voltage windings, this test stresses the entire insulation system to verify all live-to-ground clearances.
• Induced potential: Verifies the turn-to-turn and layer-to-layerinsulation at twice the rated voltage
• Loss test: These design verification tests are conducted to ensure that guaranteed loss values are met and that test values are within design tolerances; tests include no-load loss and excitation current along with impedance voltage and load loss
• Leak test: Pressurizing the tank to 5 psig assures a complete seal, with no weld or gasket leaks, to eliminate the possibility ofmoisture infiltration or oil oxidation

 

More Substation transformers

 

latest company news about Substation transformer  3latest company news about Substation transformer  4latest company news about Substation transformer  5

 

banner
News Details
Home > News >

Company news about-Substation transformer

Substation transformer

2025-03-11

WINLEY’s substation transformers are designed, built, and tested in accordance with the highest industry standards including NEMA, ANSI C.57, DOE, and IEEE as applicable, The capacity ranges from 150Kva to 20000Kva, the primary voltage range is usually 2.4KV-69KV, and the secondary voltage range is usually 0.6KV-35KV, widely used in various utilities or small industrial scenarios.

 

latest company news about Substation transformer  0

 

 

WINLEY’s substation transformers are designed, built, and tested in accordance with the highest industry standards including NEMA, ANSI C.57, DOE, and IEEE as applicable, These substation transformers are absorb and utilize advanced domestic and foreign technologies to optimize the transformer core, coil, body, lead wire, oil tank and other components. They have the characteristics of low partial discharge, low loss, low noise, light weight and long service life.

 


 

Design capabilities

 

Capacity 150Kva-20000Kva
Primary Vollage 2.4kV/4.16kV/4.8kV/6.9kV/7.2kV/12kV/12.47kV/13.2kV/13.8kV/23kV/34.5kV/44KV/69KV or other
Secondary Voltage 208Y/240/480/600/2400/4160Y/4800/12000/12470/13200/13800 or other
Connection type Dyn1Dyn11YNd1Dd0
Insulation Fluids ONAN / ONAFKNAN / KNKF
Frequency 50Hz、60Hz
BIL 30V-250V
Standards ANSI/IEEE C57
CSA
NEMA
ASTM

 

Substation transformer structure

 

WINLEY’s substation transformers incorporate advanced domestic and foreign technologies to optimize components such as the transformer core, coil, body, lead wire, and oil tank. These transformers are characterized by low partial discharge, low loss, low noise, lightweight, and long service life. They are designed for installation in both large and small three-phase transmission and distribution power systems.

 

latest company news about Substation transformer  1

 

Substation transformer Standard Features

 

  • Electrical grade mineral insulating oil
  • High-grade silicon-steel core
  • Aluminum windings (distribution class)
  • On-load tap changer
  • Reinforced carbon steel tank
  • Lifting lugs
  • Externally clamped high- and low-voltage bushings
  • Pressure relief valve
  • Pressure vacuum gauge
  • Liquid temp gauge
  • Liquid level gauge
  • Drain and sample valve
  • Schrader valve
  • Ground pads/lugs
  • Nitrogen blanket
  • 65 degree C rise

Substation transformer Optional Features

  • Environmentally friendly, high fire-point FR3 oil (KNAN)
  • Copper windings
  • On-load tap changer
  • Stainless steel tank
  • Gauges with contacts
  • Auxiliary control cabinet
  • Winding temperature indicator
  • Fan package (ONAN/ONAF)
  • Lid-mounted pressure relief device
  • Sudden pressure relay
  • Lightning arresters
  • 55/65 degree C rise
  • Step-up solar and wind duty design
  • Electrostatic shielding
  • K-rated design
  • Primary load-interrupter switch

 

Substation transformer drawing

 

Substation transformer high-voltage and low-voltage cables connect through bushings on the throat-type side end or the top, while their flexible core/coil and tank construction ensure that dimensional requirements can be met.

 

latest company news about Substation transformer  2

 

Substation transformer Specification

 

Rated Capacity High Voltage Low Voltage Connection Symbol Short Circuit Impendence No-load loss On-load loss Dimension Weight
(kVA) (KV) (V)   (%) (W) (W)

W*H*D

mm

kg
800 4.16KV
12.47KV
13.2KV
13.8KV
24.94KV
34.5KV
or others
208/120V
480/277V
600V
12470V
13200V
13800V
or others
Dyn1
Ynyn0
Dyn11
Dd0
Ynd11
or others
2.7
3.1
4.35
5.75
6
980 9350 1060*1500*1780 2050
1000 1160 11500 1085*1570*1800 2450
1250 1380 13900 1160*1610*1890 2900
1600 1660 16600 1190*1630*1950 3400
2000 2030 18300 1260*1700*2090 4100
2500 2450 19600 1150*2150*2250 4750
3000 3240 26500 1900*2600*2150 6500
5000 4500 27000 2500*2210*3180 9500
7500 7200 32000 3660*3100*5100 13600
10000 8500 35500 3830*2640*2216 15800

 

Testing


WINLEY performs routine testing on each transformer manufactured,including the following tests:
• Ratio, polarity, and phase relation:Ensures correct winding ratios and tap voltages; checks insulation of HV and LV circuits; checks entire insulation system to verify all live-to ground clearances.
• Winding resistance:Verifies the integrity of internal high-voltage and low-voltage connections; provides data for loss upgrade calculations
• Insulation power factor:Verifies that vacuum processing has thoroughly dried the insulation system to required limits
• Routine impulse tests:The most severe test, simulating a lightning surge;applies one reduced wave and one full wave to verify the BIL rating
• Applied potential: Applied to both high-voltage and low-voltage windings, this test stresses the entire insulation system to verify all live-to-ground clearances.
• Induced potential: Verifies the turn-to-turn and layer-to-layerinsulation at twice the rated voltage
• Loss test: These design verification tests are conducted to ensure that guaranteed loss values are met and that test values are within design tolerances; tests include no-load loss and excitation current along with impedance voltage and load loss
• Leak test: Pressurizing the tank to 5 psig assures a complete seal, with no weld or gasket leaks, to eliminate the possibility ofmoisture infiltration or oil oxidation

 